Description
Function | Parameter |
Model | FEVDS135 Flameless Quench Device |
Static activation pressure | Relevant to the selection of the venting element.Default valve is 0.01MPa±25%. |
Maximum reduced explosion overpressure | pred,max≤0.0451MPa |
Venting efficiency | 66% |
Flameless performance | No sparks or flame |
Reusable | No reusable |
Optional accessories | Back pressure support, explosion venting detector. |
Consumables | explosion venting membrane (venting or rapture panel). |